This product is applicable to the power transmission and distribution line with AC rated voltage(U0/U) of 3.6/6kV-26/36kV system.It is routed in air (cable bridge frame,indoor wall support,and tray) and soil(direct buried, cable trench,pipe ect.) respectively according to difference of the protection layer structure.
Construction
1 ..... Stranded bare copper
2 ..... inner layer of semi-conducting material
3 ..... core insulation of cross-linked polyethylene
4 ..... outer layer of semi-conducting material
5 ..... semi-conducting tape
6 ..... screen of copper wires
7 ..... Fillers strip, Yarn, or Paper
8 ..... Non woven Wrapping tape or Flame Retardant
9 ..... Extruded PVC Inner Covering
10 .... Stainless Steel Wire Armoured
11 .... Overall Sheath: polyvinylchloride (PVC) or FR-PVC, PE, LSOH
MV(11kv 15kv 33kv) Power Cable | ||
Model and Description Uo/U(Um)=3.6/6(7.2), 6/6(7.2), 6/10(12), 8.7/10(12), 8.7/15(17.5), 12/20(24), 18/30(36), 21/35(40.5), 26/35(40.5)kV | No.of Core | Conductor cross-section area(mm2) |
xlpe insulation | 1 core 3 core | 10 16 25 35 70 95 120 150 185 240 300 400 500 630 sq mm |
Cu core | ||
YJV, N2XSY;PVC sheathed power cable | ||
YJV22;steel tape armoured,PVC sheathed power cable | ||
YJV32,YJV42;steel wire armoured ,PVC sheathed power cable | ||
Al Core | ||
YJLV, NA2XSY; PVC sheathed power cable | ||
YJLV22;steel tape armoured,PVC sheathed power cable | ||
YJLV32,YJLV42;steel wire armoured ,PVC sheathed power cable |
Application
Used in transformer stations, switching blocks, in electric power plants and industrial plants. Medium voltage power cable for static application in ground, within and outside facilities, outdoor, in cable canals, in water, in conditions where cables are not exposed to heavier mechanical stress and tensile strain.
Standards
International: IEC 60502-2, IEC 60228
China: GB/T 12706.2-2008
Other standards such as BS,DIN and ICEA upon request
Technical data:
Test voltage | 6 / 10 kV | [kV] | 21 / 5 min. |
12 / 20 kV | [kV] | 42 / 5 min. | |
18 / 30 kV | [kV] | 63 / 5 min. | |
Temperature range | in motion | -20°C till +90°C | |
fixed | -20°C till +90°C | ||
Operating temperature | short circuit | °C | 250 |
Short circuit time | max. | [sec] | 5 |
Bending radius | min. | x diameter | 15 |
Flammability | standard | EN 50265-2-1 |
PACKING AND SHIPPING
All cable For exporting are well packed and protected by wooden drum or Wood and Steel Drum. The packing material is depended on the weight and size of cable. After the well packed cable drums sent to Sea Port, they are loaded into 20 FT container or 40 FT container. All cable drum are firmly fixed by safety belt to make sure, no movement during the sea freight. The size of the container is chosed according to weight of total loaded goods or as per the client's requirement.