Product Details
Application:
Indoor Or Outdoor Places
Rated Voltage:
0.6/1kV
Insulation:
PVC/XLPE
Sample:
Free For 10cm
Number Of Cores:
1,2,3,4,5
Jacket Color:
Orange Or Optional
OEM:
Yes
Highlight: 

fire resistant wire

,

fire proof electrical cable

Payment & Shipping Terms
Minimum Order Quantity
200m
Price
USD0.03-50
Packaging Details
100m/roll or customized
Delivery Time
As per requirement
Payment Terms
L/C,T/T
Supply Ability
10KM per Week
Product Description

0.6/1kV CU/XLPE/LOZH Fire Resistant Cable Indoor / Outdoor Electrical Cable

 

Specifications

XLPE insulated power cable,0.6-35KV,producing under IEC,BS,ASTM,DIN standard and OEM basis.

Al/Cu Conductor XLPE Insulated Thin/Thick steel armored PE Sheathed Power Cable.
Executive Standard:It is manufacture under GB/T12706-2002 standard(The same as IEC60502).


Application:


It is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable and in partial replace of PVC insulated power cable.


Using features:


1. Rated voltage: Uo/U: 26/35kV, 21/35kV, 12/20 kV (24 kV), 8.7/10kV, 8.7/15kV, 6/6kV, 6/10kV.
2. No. of core: Single-core, Three-core.
3. The highest allowed operating temperature of conductor for long-term working is 90oC. In short-circuit (Max. Long-term is no more than 5 seconds). The highest temperature for conductor is no more than 250.
4. D.C Resistance of the conductor complies with the stipulations of GB/T3956-1997.
5. The environment temperature should be no lower than 0 when lay. Otherwise it should be preheated.
6. The cable is laid without horizontal drop limit. The Min. Bending radius of three-core cable should be no smaller than 12 times of cable outer diameter.
7. Working Frequency Voltage Test:.


For cable with Uo of 3.6kV or lower: 2.5Uo+2kV/5min without puncture.
For cable with Uo of 3.6kv~18kV: 3.5Uo/5min without puncture.
For cable with Uo of 21kV and 26 kV: 2.5Uo/30min without puncture.


8. Partial Discharge Test: The discharge volume should be no more than 10pC under 1.73Uo for the cable.

 

This series includes:

 

Copper (aluminum) core, XLPE insulated and sheathed power cables.
Copper (aluminum) core, XLPE insulated, PE sheathed power cables.
Copper (aluminum) core, XLPE insulated, steel tape armoring PVC sheathed power cables.
Copper (aluminum) core, XLPE insulated, steel tape armoring, PE sheathed power cables.
Copper (aluminum) core, XLPE insulated, steel wire armoring, PVC sheathed power Cables.
Copper (aluminum) core, XLPE insulated, steel wire armoring, PE sheathed power cables


Rated voltage: 0.6/1kV,

 

Number of cores: 1 to 6.


Relative manufacturing standards: IEC60505, BS, DIN.

 

Packing: Wooden drum, steel wooden drum.

 

Power Cable


-Conductor:
Solid or stranded copper
 

-Insulation:

Cross-linked polyethylene( XLPE or PVC)


-Circuit Identication:
The insulation shall be red, black


-Filler:
Polypropylene lament with lapped binding tape


-Inner Sheath:
Polyvinyl chloride (Black)


-Armor:
Galvanized steel wire


-Core-covering:
Binding tape


-Outer Sheath:
Polyvinyl chloride (Black)


-Application:
For use in ducts, trays and direct burial in ground. The cable is subject to immerse in water all the time.


-Standards / Testing Specications:
IEC 60502-1.

 

0.6 / 1kV CU / XLPE LOZH Fire Resistant Cable Indoor / Outdoor Electrical Cable

 
 

 

 