Send Message
Qingdao Yilan Cable Co., Ltd. 86-- 18724796885 atwood.lee@hold-one.com
0.6/1 KV 3+1/2 Core XLPE Insulated Cable For Energy Supply , Underground

0.6/1 KV 3+1/2 Core XLPE Insulated Cable For Energy Supply , Underground

  • High Light

    xlpe power cable

    ,

    cross linked polyethylene cable

  • Name
    XLPE Insulated Cable
  • Conductor Material
    Copper
  • Wrapping
    XLPE (Chemical)
  • Outer Sheath
    PVC
  • Working Degree
    90℃
  • Type
    0.6/1 KV 3+1/2 Core
  • Place of Origin
    China
  • Brand Name
    HOLD-ONE
  • Certification
    CE/IEC/KEMA/VDE
  • Minimum Order Quantity
    Negotiable
  • Price
    Negotiable
  • Packaging Details
    Iron-wooden Drum or Whole Wooden Drum
  • Delivery Time
    8-15 days
  • Payment Terms
    L/C, T/T
  • Supply Ability
    100km per Month

0.6/1 KV 3+1/2 Core XLPE Insulated Cable For Energy Supply , Underground

0.6/1 KV 3+1/2 Core XLPE Insulated Cable For Energy Supply , Underground

 

XLPE Insulated Cable APPLICATIONS:

 

Power cables for energy supply are installed in open air, in underground, indoors, in cable ducts, power stations, residental connections and street lighting as well as in subscriber networks, where mechanical damages are not be expected.

 

XLPE Insulated Cable CONSTRUCTION:


1. CONDUCTOR
– Bare copper conductor, Class 2 to IEC 60228
2. INSULATION
– XLPE Compound
3. FILLER
– PP filler
4. WRAPPING TAPE
In case of armored cables:

5. INNER SHEATH
– PVC Compound
6. ARMOR
– Galvanized Double Steel Tape.
7. OUTER SHEATH :
– PVC Compound
Sheath colour :
– Black
*Note: when required for a particular application, other colors are available.

 

USAGE CHARACTERISTICS

 

Permissible operating temperature at conductor +90°C
short circuit temperature ( duration max. 5 s) 250 °C
Minimum installation temperature should not be lower than 0°C
Max. conductor permissible tensile stress 50 N/mm²
Minimum bending radius 15 x cable Ø

 

PHYSICAL AND ELECTRICAL CHARACTERISTICS:

 

No.cores x
cross-sec.
Insulation
thickness
Sheath
thickness
Nominal
value
Outer Ø
approx.
weight
approx.
Current ratings in air 30℃ Current ratings buried 20℃
Phase Neutral
mm² mm mm mm mm kg / km A A
3×4+1×2.5 0.7 0.7 1.8 12.7 277 37 47
3×6+1×4 0.7 0.7 1.8 13.9 363 47 60
3×10+1×6 0.7 0.7 1.8 16.1 527 64 81
3×16+1×10 0.7 0.7 1.8 18.6 766 85 106
3×25+1×16 0.9 0.7 1.8 22.2 1140 113 137
3×35+1×16 0.9 0.7 1.8 24.6 1475 139 164
3×50+1×25 1.0 0.9 1.8 27.7 1951 173 198
3×70+1×35 1.1 0.9 1.9 31.9 2662 222 246
3×95+1×50 1.1 1.0 2.1 36.2 3578 271 293
3×120+1×70 1.2 1.1 2.2 39.9 4567 318 334
3×150+1×70 1.4 1.1 2.3 45 5514 370 375
3×185+1×95 1.6 1.1 2.5 49.4 6850 427 422
3×240+1×120 1.7 1.2 2.7 54.9 8741 507 492
3×300+1×150 1.8 1.4 2.9 62.9 11052 599 560